|
|
|
|  |
Fuel Tank Emergency Procedure and SPCC Plan
Policy ID: SH-19
Date Instituted: December 1, 2000
Last Revised: November 11, 2005
Policy Description
Executive Summary
(Click
here for PDF)
Purpose: The Fuel Tank Emergency Procedure and SPCC Plan
describes the facility’s response guidelines to control and remove the
released materials and the steps to follow to place all human lives
affected by the release out of harm’s way.
Sources: The most significant sources of hazardous material that
can be released to the environment are Diesel Fuel #2 and gasoline.
Diesel is stored in ten (10) tanks in various locations within the two
campuses. Gasoline is stored in a single 1000-gallon UST in the
Security Building located in the Main Campus.
Inspections: In order to maintain and assess the integrity of
the fuel tanks, monthly inspections will be carried out and documented
by qualified personnel. There is a checklist form that will be used to
document these inspections.
Spills: In case of a spill, the responding personnel must assess
whether there has been a release to the environment or not. If so, the
appropriate State or Federal agencies will be notified as detailed in
the procedure. In order to minimize the spilled fuel, the system
(boiler, generator or pump) will be shutdown and isolated, and the Fire
Department will be notified at once. In addition, for large spills, an
outside contractor will be called to completely clean up the spill and
dispose of the wastes generated by the clean up efforts. The MSDSs of
Diesel Fuel #2 and Gasoline have been included for reference and
emergency response information.
Fires: In the event of a fire, the local Fire Department will be
called. In order to minimize the potential of fire, a Hot Work Permit
system will be implemented. Other security measures will be aimed at
keeping these sensitive areas off-limits to non-building personnel to
prevent unauthorized operation, sabotage or bomb threats. In addition,
special security procedures will be followed during construction and
emergencies around the tanks. All affected personnel will be trained
annually via lectures and hands-on practices.
1.0 Introduction
1.1 Objective
The Emergency Procedure and Spill Prevention Control and Countermeasure
(SPCC Plan from hereon) describes Seton Hall University (SHU)
preparedness to prevent the discharge and release of fuel oil, gasoline
or of a hazardous product or waste into the environment. In the event
of accidental release, the Emergency Procedure and SPCC Plan describes
the facility’s response to control and remove the released materials
and the steps to follow to place all human lives affected by the
release out of harm’s way.
1.2 Purpose
The intent of the Emergency Procedure and Spill Prevention Control and
Countermeasure (SPCC) Plan is to satisfy the requirements of OSHA’s
Emergency Response to Hazardous Substance Releases (29 CFR 1910.120
(q)) and Flammable and Combustible Liquids handling (29 CFR 1910.106).
The Clean Water Act (CWA), the Resource Conservation & Recovery Act
(RCRA), and the Comprehensive Environmental Response, Compensation and
Liability Act (CERCLA). Moreover, the SPCC plan was prepared to satisfy
EPA regulations on Oil Pollution Prevention (40 CFR Part 112) and on
Contingency Plan and Emergency Procedures for hazardous waste
generators and treatment, storage and disposal facilities [40 CFR
262.34 (a), 262.52 (a) and 265.52 (a)].
The SPCC Plan identifies potential sources of oil and hazardous
substances and the measures required to prevent and contain any
accidental discharge resulting from equipment or storage facility
failure. The Emergency Procedures are designed to prevent injuries or
illnesses to employees, contractors, students and visitors at the
facility during or immediately after the hazardous substance release.
The Procedure also outlines steps to follow during other emergency
scenarios, such as fires, bomb threats or security breaches.
1.3 Location
Seton Hall University (SHU), founded in 1856, occupies 56 acres in
South Orange, NJ at the foot of South Mountain. The street and mailing
address is 400 South Orange Avenue, South Orange, NJ 07079.
1.4 Type of Operation
Seton Hall University was founded in 1856 by the first bishop of
Newark. It is the oldest and largest diocesan university in the U.S.
The 56-acre main campus in South Orange is about 14 miles from New
York, at the foot of South Mountain. Two campuses in South Orange and
Newark house eight schools comprised in 43 buildings constructed
between 1856 and 1997. The university has never ceased to function as
an educational institution since its inception. Current enrollment is
over 10,000 students.
The university has a total of eight (8) diesel-powered emergency
generators. seven (7) generators are located in different buildings on
the Main Campus in South Orange and one (1) is in the basement of the
Law School Building in Newark, NJ. In addition to these generators, the
Main Campus also has three (3) bulk diesel fuel tanks and one (1) bulk
1,000-gallon gasoline underground storage tank (UST) that have the
potential for discharging diesel fuel or gasoline into the environment.
Two (2) of the bulk diesel tanks are also USTs with a 20,000-gallon
capacity each. Overall, Seton Hall University has 41,000 gallons of
fuel stored underground and about 2,600 gallons of fuel stored above
ground, for a total maximum fuel storage capacity of approximately
43,600 gallons.
The university has re-designed the fuel off-loading stations for the
bulk storage tanks to include secondary containment of the tank trucks
delivering bulk fuel on campus.
2.0 Spill Prevention Control and Countermeasure Plan
Guidelines
2.1 General Information
2.1.1 Name of Facility: Seton Hall University (SHU)
2.1.2 Type of Facility: Educational institution housed in
several buildings in two distinct campuses in South Orange and Newark,
NJ.
2.1.3 Locations of Facility: Main Campus: 400 South Orange Ave.
South Orange, NJ 07079
Newark Campus: Law School Building One Newark Center, Newark, NJ
2.1.4 Designated personnel accountable for oil spill prevention
at this facility:
Roger Demareski
|
AVP Administration
|
Steve Kurtyka
|
Physical Plant Director
|
Craig Stapfer
|
Facilities Engineering Safety Coord.
|
Leon Vandermeulebroke
|
Assistant Director Physical Plant
|
Marty Kropp
|
Chief Engineer
|
Tom LeCompte
|
Assistant Chief Engineer
|
2.1.5 This facility has not experienced a reportable oil spill
event during the twelve months prior to January 10, 1974, the effective
date of 40 CFR, Part 112.
2.2 Management Approval
This Emergency Procedure and SPCC Plan will be implemented as herein
described.
Signature __________________________________
Name and Title ______________________________________________
2.3 Certification
I hereby certify that I have examined the facility, and being familiar
with the provisions of 40 CFR, part 112, attest that this SPCC Plan has
been prepared in accordance with good engineering practices.
Printed Name of Registered Professional Engineer _____________________
Signature of Registered Professional Engineer
__________________________
Seal & Registration Number _____________ State ____ Date _________
2.4 Potential Spill-Prediction and Control
The sources of potential spills and how to control them are listed
below.
2.4.1 Potential Sources of Spills. There are
twelve (12) separate sources that can fail or rupture and accidentally
release diesel fuel or gasoline into the environment at this facility:
There are eight (8) diesel emergency generators, two (2) bulk USTs and
one (1) bulk AST tank that are used to store No. 2 Diesel Fuel on
campus. There is also one (1) UST to store bulk gasoline buried near
the Security Building. In addition to these tanks, there are two fill
stations where tank trucks bring and unload fuel into bulk ASTs or
USTs. The identified potential sources of spills are listed below:
2.4.1.1 Boiler House UST tanks: Two 20,000 Gallon No. 2
diesel fuel bulk underground storage tanks located under the parking
area south of the Boiler House and east of Lewis Hall.
2.4.1.2 McNulty Hall Emergency Generator tank: One 626-gallon
No. 2 diesel fuel belly tank directly beneath the generator, located on
the parking lot north of McNulty Hall.
2.4.1.3 Corrigan Hall Emergency Generator tank: One 500-gallon No.
2 diesel fuel belly tank directly beneath the generator, located on the
south side between Corrigan and Aquinas Halls.
2.4.1.4 Security Center: There are two tanks at this location:
2.4.1.4.1 One 1000-gallon underground storage tank
(UST) for bulk gasoline located in the parking lot.
2.4.1.4.2 One 275-gallon aboveground storage tank (AST) for bulk
diesel fuel located in the basement of the building.
2.4.1.5 Walsh Library Emergency Generator tank: One
130-gallon No. 2 diesel fuel belly tank directly beneath the generator,
located in the basement of the building (indoors).
2.4.1.6 Brennan Recreational Center Emergency Generator tank: One
120-gallon No. 2 diesel fuel belly tank directly beneath the generator,
located on the northeast parking lot of the building.
2.4.1.7 Jubilee Hall Emergency Generator tank: One 346-gallon
No. 2 diesel fuel belly tank directly beneath the generator, located on
the grounds east of Jubilee Hall.
2.4.1.8 Power Plant Emergency Generator tank: One 200-gallon No.
2 diesel fuel belly tank located on the roof of the Power Plant
building. It has a double wall tank with leak detection sensors and
alarm system. (Roof Mounted)
2.4.1.9 Bulk transport vehicles (tank trucks) delivering liquid
fuel at off-loading stations. The two most likely locations are:
2.4.1.9.1 The area immediately above the fill ports
for the two 20,000-gallon diesel fuel USTs south of the Boiler House.
2.4.1.9.2 The fill stations for the 1,000-gallon gasoline UST
and the 275-gallon diesel fuel AST located in the parking lot southeast
of the Security Building.
2.4.1.10 Portable Emergency Generator tank: One 115-gallon
No. 2 diesel fuel belly tank directly beneath the generator, mounted on
a trailer and located on the Power Plant parking lot.
2.4.1.11 Hydraulic sumps for elevators and other miscellaneous
small hydraulic oil reservoirs throughout the campuses. These are
deemed low risk / low impact because of the small amounts of liquid
involved at each source.
2.4.1.12 Law School Building Emergency Generator tank: One
1000-gallon No. 2 diesel fuel AST tank located inside the Boiler Room
on the lower level of the Law School building in Newark, NJ (indoors).
2.4.2 Secondary and tertiary Containment: All possible
sources of major spills have spill-containment provisions, such as
concrete pads and berms surrounding the main storage vessels.
2.4.3 Diversionary Structures Or Equipment To Prevent Fuel
Oil From Reaching Navigable Waters: All potential spill sources
identified above have been identified and adequate containment
materials have been procured and stored on site. Emergency spill
containment kits are available in the vicinity of each potential source
or readily available by emergency responding personnel. Whenever
possible, locations with nearby storm drains or bodies of water that
can carry spill overflows to navigable waters have been diked or
protected with tertiary spill containment systems. Wherever necessary,
drain plugs and absorbent booms have been included inside the spill
kits to prevent spills from reaching the storm sewer system.
2.5 Inspections and Records
2.5.1 Inspection Procedures:
2.5.1.1 In addition to the daily inspections by the
Physical Plant personnel, a designated employee will visually inspect
and document the entire area for integrity of the equipment and
readiness of the spill prevention systems in place. The inspections
will be conducted at least monthly and will be documented through the
attached checklist below. As a minimum, the inspection will include the
status of:
- Housekeeping
- Individual tanks or pumps
- Piping systems, including valves and flanges
- Containment walls, dikes or vessels
- Lighting and security
- Emergency lighting
- Fire extinguishers, sprinkler system
- Spill Kit(s)
- Labels, “No Smoking” and Warning Signs
2.5.1.2 If any deficiencies are noted, appropriate
steps will be taken to correct the deficiency within a reasonable time.
Once corrected, a note should be made or attached to the original
inspection checklist indicating how and when the deficiency was
corrected.
Note: In the event that a major spill is detected,
the Emergency Spill Procedure will be triggered immediately to contain
and clean up the spill. Notify the Office of Public Safety (ext. 9300)
in the event of a spill or release.
2.5.1.3 The inspector will sign and date the checklist form and
will file it in an accessible folder or binder stored in the Physical
Plant office.
2.5.1.4 The inspection forms will be reviewed annually for
trends and kept on the active file for at least 3 years.
2.5.2 Inspection Checklists: To simplify the record
keeping and documentation of inspections and audits carried out by
Seton Hall University personnel, a checklist is presented below and
recommended for each monthly inspection. Although each checklist
includes the minimum items to be checked, they are not all-inclusive
and should be revised to add or delete items needed or not needed as
changes and/or modifications to the sites occur.
2.6 Spill Procedures
In the event of a spill or accidental release of fuel oil or other
combustible material on premises, Seton Hall University personnel will
follow the procedure outlined below. Diesel Fuel #2 is considered a
Class II Combustible Liquid, Gasoline is a Flammable Liquid (see
attached MSDSs for additional information about Diesel Fuel #2 and
Gasoline).
2.6.1 Reportable Quantities (RQ): Under New Jersey’s
environmental law, ALL spills are reportable and there are no minimum
reportable quantity (RQ) for any listed combustible or flammable
substance in liquid form. Combustible substances, such as diesel fuel,
are those liquids with a flash point at or above 100°F (37.8°C) and
below 300°F (148.9°C). Flammable substances, such as gasoline, are
those liquids with a flash point at or below 100°F (37.8°C). Several
agencies must be notified upon an accidental release of a listed
hazardous substance into the air, ground or body of water and which
presents a danger to the public and/or the environment. In addition,
these agencies may be notified if the volume of a contained spill
exceeds the total capacity of the secondary or tertiary containment
around the tank(s).
2.6.2 Government Agency Contacts: If any amount of Diesel
Fuel #2 or gasoline is accidentally released into the environment (air,
ground or water), the secondary containment of the tank suffers
catastrophic failure, or the released fuel presents a danger to the
public, then notify the proper government agency as outlined below:
2.6.2.1 Call immediately 911 and the NJDEP at (877)
927-6337 (WARN DEP)
2.6.2.2 If needed, call the National Response Center at (800)
424-8802.
2.6.2.3 Identify:
- Facility Name, Address, phone numbers and contact persons.
- The substance released, form and quantity involved.
- Water, ground or air contamination.
- Time the incident happened and for how long.
2.6.2.4 Summarize precautions to be taken:
- Health and physical hazards.
- Medical needs.
- Emergency evacuation.
2.6.2.5 Within a week of the release, send the NJDEP
a written notification of the incident by certified mail and include:
- Facility Name, Address, phone numbers and contact persons.
- The substance released, form and quantity involved.
- Water, ground or air contamination.
- Time the incident happened and for how long.
- The nature of the process(es) or operations that take place at the
site, including those involved in the actual release.
- Climatological conditions that contributed to the incident.
- Injuries or illnesses caused by the release.
- Abatement or clean up measures taken to control the incident.
- Any additional details requested by the NJDEP at the time of the
telephone notification.
2.6.2.6 Submit the written notification by certified mail to
the following address:
Division of Hazardous Materials Management
Department of Environmental Protection (DEP)
Trenton, NJ
Attn: Hazardous Substances Emergency Response Officer
2.6.3 Shut Down and Notification Procedure: Once
alerted of the spill, follow the procedure that follows:
- Notify the Office of Public Safety at ext. 9300.
- Proceed to shutdown the pumping equipment related to the leaking
tank or tanker truck.
- If provided, close the emergency shut off valve(s) associated with
secondary containments with storm basins and/or overflow tanks. These
are located in the Boiler Room and Security Building parking lots
(containment areas) in case of tanker truck spills.
- Secure the area and wait for the Fire Department to arrive at the
scene of the incident. Instruct the guards posted at each gate to
direct the responding agencies to the exact location of the spill.
- For large spills, immediately call outside contractors as listed in
section 2.6.4 below.
- Make sure there are no sources of ignition present and call for
help if additional help has not arrived yet.
- Assess the extent of the spill and determine if a reportable
quantity was released to the environment (air, ground or water). If so,
then contact the appropriate government agency as outlined in Item
2.6.2 above and wait for them to arrive at the scene. Have someone
outside ready to direct them to the scene of the spill.
- If there has been NO release to the environment and the spill has
been successfully brought under control, proceed to clean up the
spilled fuel oil as per (10) or,
- Call the 24-Hour Spill Response Service vendor listed in 2.6.4
below and arrange for the spill’s clean up and waste disposal outside
services. Skip to (11).
- Utilizing the non-sparking tools in the room and an empty drum for
disposal, clean up and pick up all spilled fuel oil and oil-soaked
absorbent material and place it in the drum for later disposal. Put a
lid over the drum to contain any fuel vapors.
- Insure that there are no sources of ignition present and that spill
response efforts DO NOT introduce potential sources of ignition.
Maintain the area secured and off-limits to non-responding
personnel.
- Arrange for further clean up, packing and disposal of all the
wastes generated by the spill.
- Investigate the source and causes of the incident and determine the
best permanent corrective actions to avoid re-occurrence of the
incident.
- Prepare a written report of the investigation, review it and
discuss it with the Risk Management or Lab Safety committee, and file
it for future reference.
- If necessary, critique the spill response efforts and revise these
procedures as per the changes, additions or deletions suggested during
the incident response critique session(s).
- Replenish or replace any Spill Kit(s), tools or emergency response
items spent or lost during the spill response incident.
2.6.4 24-Hour Emergency Response Service and Waste
Disposal:
H.M.H.T.T.C. Hazardous Materials Emergency Response
P.O. Box 8630
Elizabeth, NJ 07208
Tel (800) 927-9303
Fax (908) 558-6162
South Orange Fire Department
Telephone: 911
Telephone: (973) 762-3200
Or, for Waste Disposal contact:
Turnkey Environmental Services
Telephone: (908) 362-1153
Cell: (908) 310-8608
Contact: Mr. Bob Greco
2.6.5 Medical Emergencies: All medical emergencies
will be handled by calling 9300 and waiting for an ambulance to arrive
at the site. Follow the steps below:
- Do not move the person. If qualified, administer first
aid.
- Call Public Safety at 9300 to summons an ambulance to your
location. Tell them your name and location (Building, room) and the
issue at hand.
- Post one person at the lobby or outside of your building to lead
the medical team to the person in distress.
2.6.6 MSDS's: The Material Safety Data Sheets (MSDSs)
for Diesel Fuel #2 and Gasoline are attached for reference and
emergency response information. Other MSDS are available upon request
by calling the 3E Company at 800-360-3220.
3.0 Fire Prevention and Other Emergency Procedures
This section outlines the procedures to follow in the event of a fire,
bomb threat, or security breaches in or around the different
diesel-powered generators, diesel fuel tanks or the gasoline fuel tank
on campus.
3.1 Fire Prevention
Aside from spills, the threat of a fire is the second most likely and
dangerous hazard related to the fuel tanks located at Seton Hall
University. There must be good coordination of personnel and incidence
command procedures implemented to take full advantage of those safety
systems already in place to minimize property loss and eliminate injury
or illness hazards to human life.
3.1.1 Ignition Sources: Diesel Fuel Oil #2 is
an OSHA Class II combustible liquid, with a flash point of 125°F. Its
volatility is similar to that of gas oil; therefore, its vapors may
travel to a source of ignition and flash back. In order to minimize the
potential of accidental fire, all sources of ignition inside the room
should be eliminated or rendered harmless by approved engineering or
administrative controls. Typically, these controls will include among
others:
- Sealed or explosion-proof electrical systems for sources located in
enclosed environments.
- Low voltage (24-Volt) lights or tools in the event that auxiliary
lights or portable tools are needed during repairs or maintenance
inside the tanks.
- Hot Work Permit system for all Welding, brazing, burning, cutting,
soldering, grinding, thawing or any temporary operation involving open
flames or producing heat and/or sparks.
- Smoking prohibited inside the tanks or in the vicinity of the
tanks.
3.1.2 Hot Work Permit System: Hot Work is any work
involving electric or gas welding, cutting, brazing, burning or similar
flame- or spark-producing operations. This includes, but is not limited
to, acetylene torches, arc welding equipment, portable grinders,
propane torches, explosion-actuated tools, etc. All hot work to be
conducted at the building by employees or contractors should be
properly authorized and permitted using the following Hot Work Permit
Procedure No. FE-13.
Under the Hot Work Permit system, a form is used to authorize hot work
on premises. It lists the minimum fire precautions to take, nature and
location of the work to be performed, date and time work will commence,
emergency numbers and authorization signature. The permit is to be
posted at the work site until the hot work is completed and then kept
on file for at least 90 days.
3.2 Bomb Threats
Bomb threats must be seriously taken due to the great potential for
injury to human lives and property damage. In the rare event of a bomb
threat by telephone, do as follows:
3.2.1 Attract the attention of a co-worker
discreetly and quietly (while listening to the caller) have the
co-worker call 9300 and ask the Public Safety Officer on call to
request the police that the call be traced and provide expert help.
3.2.2 Get as much information as possible from the caller about
the location and type of bomb, its detonation time and the reason for
its placement. Ask about its appearance and who is placing it.
3.2.3 Ask the caller to repeat parts of the message and make
notes of any clues that might help the police, such as: Is the caller
male or female? Adult? Juvenile? Is the voice educated or coarse? Does
he have an accent or a distinguishable voice? Does the person seem
angry, rational, deliberate? Make notes of background music or noise.
3.2.4 Call the University switchboard and communicate the
incident. He or she will notify the Compliance Officer and the police.
3.3 Security Procedures
Security procedures are already in place for normal operation of the
generators or boilers on campus. Special security measures will have to
be taken during emergencies or construction / alteration projects
inside or near the rooms or areas housing fuel tanks or generators. The
following describes the minimum-security measures to take at Seton Hall
University during normal operation, emergencies or construction
activities in or around fuel tanks, boilers and generators.
3.3.1 Normal Operation: During normal
operations, Generators, Boiler Room and Fuel Tanks will remain off
limits to non-authorized personnel.
3.3.2 Construction / Alterations: During construction,
alterations or maintenance work inside or around the fuel tanks, or
fuel storage rooms which require the door(s) to be open, security
guards or watchmen will be posted.
3.3.3 Emergencies: During emergencies such as fire or
fuel spills, a security guard or watchman will be posted once the Fire
Department finishes their emergency activities in or around the area of
the spill, declare the area safe for re-occupancy and turn the area
back to the University’s control.
4.0 Training and Education
Selected Physical Plant staff will receive training and education
commensurate with the duties they are expected to perform, on at least
an annual basis, and whenever new hazards are introduced which may
alter their duties or response.
4.1 Requirements
This training should meet minimum requirements, such as:
4.1.1 Training and education must be provided prior
to any participation in emergency operations.
4.1.2 The quality and quantity of training will ensure that
members are capable of performing their assigned duties in a safe
manner.
4.1.3 Instruction in the location, use, operation and
limitations of all emergency equipment they are expected to use,
including hands-on training.
4.1.4 Handling of site-specific hazards to which members may be
exposed during an emergency.
4.1.5 Coordination with outside agencies and their requirements.
4.2 Training Topics
As a minimum the annual training and education sessions with the
Physical Plant staff must include the following topics:
- Possible emergency scenarios.
- Emergency Procedures and SPCC Plan.
- Applicable pollution control laws, rules and regulations.
- Safe operation and maintenance of equipment to prevent
emergencies.
- First Aid and medical assistance during emergencies.
- Hands-on practices.
4.3 Practice Drills
Every year, Seton Hall University will conduct one or more drills aimed
at practicing the procedures outlined by this plan and detect any
potential deficiencies or shortcomings. Such drills should be held for
all affected emergency response personnel, at random intervals and at
least annually. When possible, drills should include local emergency
response agencies (police, fire department, etc), which should be
included in the post-drill critique sessions.
4.4 Revisions
This procedure will be revised whenever changes are introduced to the
University infrastructure that may affect the Fuel Tanks, Boiler Rooms
and Generators, or at least every three (3) years.
5.0 References
5.1 NFPA 30, “Flammable and Combustible Liquids Code”
5.2 OSHA Standard 29 CFR 1910.38, “Employee Emergency Plans and
Fire Prevention Plans”
5.3 OSHA Standard 29 CFR 1910.106, “ Flammable and Combustible
Liquids”
5.4 OSHA Standard 29 CFR 1919.120, “ Hazardous Waste Operations
and Emergency Response”
5.5 OSHA Standard 29 CFR 1910.155-156, “Fire Protection and Fire
Brigades”
5.6 EPA Standard 40 CFR 112, “Oil Pollution Prevention”
5.7 EPA Standard 40 CFR 262–265, “Contingency Plan and Emergency
Procedures for Hazardous Waste Generators and Treatment, Storage and
Disposal Facilities”
5.8 CTSI, “SH-12, Hot Work Permit Procedure”
5.9 Applicable local regulations and codes
|
|
|